Arc protection |
Bus differential protection |
Overcurrent/arc double criterion,concise, unique, reliable |
The system needs to consider CT ratio, characteristic matching, saturation, disconnection and many other factors. |
Passive light sensor,optical fiber transmission arc signal,not subject to electromagnetic interference |
Copper wire transmission current signal,anti-electromagnetic interference is relatively poor |
Whole set of action time ≤1ms |
The entire set of action time is generally required≥20ms |
Each system can accommodate 36 medium voltage switchgears (considering the configuration of three probes per switchgear) |
Generally accommodates up to 24 feeders |
The control logic is programmable, which is convenient for all kinds of bus wiring and operation mode changes, and can be fault-located. |
When the operation mode is changed, the related operations of protection are complicated, and the fault cannot be located. |
Flexible installation, whether it is a new project or a retrofit project |
Need special protection level CT, not only big investment, but also difficult for reconstruction projects |